Fire Alarm BACnet Integration — Austin Government Building
Austin, TX · Products: Custom BACnet integration panel, automation control enclosure
The Challenge
A City of Austin government building required lighting controls that integrated with the building's fire alarm system via BACnet. When a fire alarm triggered, all lighting had to go to 100% immediately. The building management system (BMS) needed real-time status of the lighting system. Standard lighting controls don't natively interface with BACnet fire alarm systems — there's usually a gap between the fire alarm panel and the lighting controller.
The Solution
Nuvospec designed and built a custom solution featuring:
- Received BACnet alarm signals from the fire alarm panel
- Translated them to relay contact closures for the lighting controllers
- Provided BACnet status feedback to the BMS (lighting zone states, alarm acknowledgment)
- Included manual override switches for facilities maintenance
- Met government procurement requirements (BAA compliant where applicable)
The Result
- Code compliance: Met all NFPA and local fire code requirements for emergency lighting integration
- Single interface: BMS operator sees lighting status alongside all other building systems
- Maintenance: Facilities team can override individual zones without calling the controls contractor
- Specification: The specifying engineer has since included this integration approach on two additional municipal projects
Key Takeaway
“Government projects often have integration requirements that no single manufacturer covers. BACnet-to-lighting, fire alarm interfaces, BMS monitoring — these are all opportunities where Nuvospec fills the gap.”
Project Details
- Market
- Government
- Location
- Austin, TX
- Products Used
- Custom BACnet integration panel, automation control enclosure