Specification Guide

How to Specify a Lighting Contactor Panel

A lighting contactor panel is usually specified in Section 26 09 23, Lighting Control Devices. The specification needs nine items: poles, contactor rating, coil voltage, enclosure, time clock, photocell, manual override, building automation interface, and factory assembly and listing. This page lists what to write for each and gives sample text to copy.

Which section does it go in?

Most specifications place lighting contactor panels in Section 26 09 23, Lighting Control Devices, with the time clocks and photocells that control them. Two other sections are also used:

  • Section 26 09 16, Electrical Controls and Relays, when a firm keeps all relays and contactors in one section or the panel switches more than lighting loads.
  • Section 26 09 26, Lighting Control Panelboards, when a firm treats a factory-assembled contactor panel as a lighting control panel.

Any of the three works. Use the one your master specification already uses. Keep the panel, its time clock and its photocell in one section so the contractor buys them as one assembly, and show the circuits on a panel schedule on the drawings.

What to specify

ItemWhat to stateNuvospec standard panels
PolesThe number of circuits each panel switches. One pole switches one circuit.CTRL-PNL: 2, 4, 6, 8, 10, or 12. CTRL-ECO: 3, 6, 9, or 12.
Contactor ratingCurrent per pole, voltage rating and the load type.30 A per pole at 600 VAC, electrically held, for all lighting load types.
Coil voltageThe control voltage available at the panel.120 VAC standard. CTRL-PNL: 277, 208 or 24 VAC. CTRL-ECO: 277 VAC supply or 24 VAC.
EnclosureIndoor or outdoor location, and whether the door must lock.Lockable steel NEMA 1 (indoor) or NEMA 3R (outdoor). NEMA 4, 4X and 12 as a custom panel.
Time clockSchedule type and whether it follows sunrise and sunset.CTRL-PNL: 7-day astronomical time clock. CTRL-ECO: digital time clock in the panel, or an outdoor astronomic time switch.
PhotocellWhether exterior lighting also responds to daylight.Exterior photocell option on both series.
Manual overrideHow maintenance staff turn the lights on outside the schedule.Hand-Off-Auto selector switch or a 2-hour override switch.
Building automationWhether another system commands the panel.CTRL-PNL: BACnet option. CTRL-ECO: dry contact input.
Assembly and listingFactory assembly and the listing the project requires.Assembled, wired and tested in a UL 508A certified panel shop from UL listed components.

Full ratings are on the CTRL-PNL datasheet and the CTRL-ECO datasheet. Check the project requirements and your local energy code for the controls the site needs.

Sample specification text

This text is written around the Nuvospec CTRL-PNL series. Choose one option wherever brackets appear, delete the controls the project does not need, and edit it to match your firm's master specification.

SECTION 26 09 23
LIGHTING CONTROL DEVICES

PART 1  GENERAL

1.1  SUMMARY
  A. Pre-assembled lighting contactor panels for time clock,
     photocell and manual switching of lighting circuits.

1.2  SUBMITTALS
  A. Product datasheet for each panel type.
  B. Wiring diagram showing line, load and control terminations.
  C. Panel schedule listing the circuits switched by each panel.

1.3  QUALITY ASSURANCE
  A. Panels shall be assembled, wired and tested at the factory
     in a UL 508A certified panel shop.
  B. Components shall be UL listed.

1.4  WARRANTY
  A. Manufacturer's 3-year limited warranty.

PART 2  PRODUCTS

2.1  MANUFACTURER
  A. Basis of design: Nuvospec CTRL-PNL series.
     nuvospec.com, (512) 615-9002.

2.2  LIGHTING CONTACTOR PANEL
  A. Contactors: electrically held, rated 30 A per pole at
     600 VAC, suitable for all lighting load types.
  B. Poles: [2] [4] [6] [8] [10] [12], as scheduled.
     One pole per switched circuit.
  C. Coil voltage: [120] [277] [208] [24] VAC.
  D. Enclosure: lockable steel, [NEMA 1] [NEMA 3R],
     gray powder coat finish.
  E. Terminals: accept 14 to 8 AWG solid or stranded copper
     conductors rated 75 C.
  F. Controls, as scheduled:
     1. 7-day astronomical time clock with backup power.
     2. Exterior photocell.
     3. Hand-Off-Auto selector switch.
     4. 2-hour override switch.
     5. BACnet interface.
  G. Panel shall ship as one assembly with components mounted,
     wired and labeled.

PART 3  EXECUTION

3.1  INSTALLATION
  A. Install in accordance with the manufacturer's instructions.
  B. Mount NEMA 1 panels indoors in dry locations. Mount
     NEMA 3R panels where exposed to weather.
  C. Terminate line, load and control conductors on the
     labeled terminals.
  D. Mount the photocell facing north, away from the lighting
     it controls.

3.2  STARTUP
  A. Program the time clock to the owner's schedule.
  B. Test each control and override, and demonstrate operation
     to the owner.

END OF SECTION

Editing the text for other panels

  • For the CTRL-ECO series, change the basis of design, set the poles to 3, 6, 9, or 12, and replace the time clock with a digital time clock in the panel or an outdoor astronomic time switch.
  • For more than 12 poles in one panel, a NEMA 4, 4X or 12 enclosure, or mechanically held contactors, specify a custom panel and describe what it has to control.
  • For exterior and site lighting, see parking lot and site lighting control for the control methods and which panel fits.

Lead time and ordering

Standard panels typically ship in 2 to 4 weeks and custom panels in 4 to 6 weeks. Standard panels cover 2 to 12 poles, and the part number guide explains each ordering code. Every order is quoted: send the panel schedule through the quote form, email sales@nuvospec.com or call (512) 615-9002.

Specification questions

Which specification section covers a lighting contactor panel?

Most specifications place lighting contactor panels in Section 26 09 23, Lighting Control Devices, with the time clocks and photocells. Some firms use Section 26 09 16, Electrical Controls and Relays, or Section 26 09 26, Lighting Control Panelboards. Use the section your firm's master specification already uses, and keep the panel, its time clock and its photocell in the same section.

What does the manufacturer need from the drawings to build the panel?

A panel schedule that lists each switched circuit, the lighting load voltage, the coil or control voltage, the enclosure type and the control method for each zone. One pole switches one circuit, so the circuit count sets the pole count. Request a quote.

Should the contactors be electrically held or mechanically held?

Nuvospec standard panels use electrically held contactors, which open when control power is lost. Mechanically held contactors stay in their last position and are quiet when closed. They are available as a custom panel. See custom panels.

Can a Nuvospec panel be the basis of design?

Yes. Name the series and the part number on the schedule. Standard CTRL-PNL panels cover 2 to 12 poles and CTRL-ECO panels cover 3 to 12 poles. Larger pole counts, NEMA 4, 4X or 12 enclosures and combined functions are built as custom panels.

What goes in the submittal?

The product datasheet for each panel type, a wiring diagram and the panel schedule. The CTRL-PNL and CTRL-ECO datasheets include wiring diagrams and can be downloaded from the product pages. For a custom panel, our team prepares the datasheet with the quote. Email sales@nuvospec.com if the specification asks for anything else.

Writing a lighting contactor panel into a specification?

Send the panel schedule and our team will confirm the part numbers.